The
field proven WorldPower UPS line is ideally suited
for military, industrial, computer and telecommunications
applications requiring high reliability, rugged construction,
compact size and light weight design. These units are
equally suited for use in shipboard, airborne, vehicular,
field deployed or fixed locations with controlled or
uncontrolled environments. The ETI0001-1250 is specifically
designed for lightweight global power deployment or
equally well in shallow depth racks.
The
heavy-duty chassis occupies only 7" (4U) of rack
space while delivering up to 1550 VA of clean, uninterruptible
power. The rounded metal corners and rugged handles,
aid in safe handling. Internally, all major components
are well secured and electrically insulated to prevent
damage due to shock and vibration. The optional heavy-duty
rack slides provide easy installation and removal of
the unit with full extension.
The
internal shielded input transformer provides galvanic
isolation with provisions for both domestic (115 VAC,
CONUS) and international (230 VAC, OCONUS) input voltages.
The autoranging input voltage selection allows inputting
either 115 VAC or 230 VAC without having to open the
UPS enclosure. Special EMI/RFI filters and input power
factor correction minimize both input current and harmonics.
The input switch and the galvanic isolation transformer
provide a double pole isolated source for shipboard
systems or overseas locations where phase references
and grounding are not consistent. Alternately, the
unit also accepts vehicular or aircraft power from
nominal 24 VDC systems. This allows the unit to be
operated when no AC source is available.
The
LED arrays keep the operator informed as to the unit's
status including load and battery levels. The high
intensity audible alarm can be heard in high noise
environments. All controls and protective devices are
brought to front and rear panels with critical switches
having finger guards. Further, all front panel devices
are recessed to prevent damage or accidental operation.
The
rear panel provides locking connectors for the input
and output power with various optional configurations
available. This reverse air flow version draws air
through the front and exhausts out the rear vent into
the rack. A removable and washable intake air filter
and high capacity stainless steel ball bearing fan
provide added protection in both controlled and hostile
environments. The batteries are maintenance free with
immobilized electrolyte and are constructed of flame
retardant materials. For more information, see the
Battery Technology section. The two status D shell
connectors provide both a contact and serial interface
with optional computer software providing loss of AC
and low battery status as well as remote shut down
capability.
See
the Power Distribution Units section for a listing
of stand alone PDUs. See the N5 Series ETI0001-1482
for a version of this UPS with an integrated PDU and
remote control
Overall,
the WorldPower line is uniquely qualified for critical
shipboard, vehicle, airborne or land based systems
combining advanced modular design features with highly
reliable construction.
Technical Specifications:
ETI0001-1250|
|
| AC OUTPUT |
| Output
voltage: |
120 VAC
true sinewave std, up to 600 VAC optional |
| Output
rating: UPS |
1550
VA, standard in 4U x 19" chassis
0.65-0.75 pf std, optional configurations to 24,000
VA |
| Non-linear
load capacity: |
Up to
100% non-linear load capability w/o derating |
| Output
voltage regulation: UPS |
± 3.0%
static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
| Overload
surge capacity: |
110%
for 10 minutes; 125% for 30 seconds |
| Harmonic
distortion: |
Less
than 5.0% into 100% non-linear load |
| Output
frequency: UPS |
60 Hz ± 1.0%
independent of input frequency |
| Operational
status |
Status,
load and battery (16) LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off |
| AC INPUT |
| Input
voltage selection: |
Autoranging
from nominal 115 VAC to 230 VAC |
| Input
voltage tolerance: UPS |
+15%
-25%, or 85-135 and 170-270 |
| Input
frequency: |
From
46 Hz to 440 Hz |
| Input
power factor: |
Better
than 99% typically |
| Input/output
isolation: |
2000
VA, >120 dB common mode, <1.0 ma leakage |
| Input
transient suppression: |
Complies
with IEEE 587 and UL 1449 |
| Input
control/protection: |
Guarded
2 pole switch (S1) w/fuse (F2) |
| Input
power connection: |
MS 3102A-22-2P,
3 pin, locking |
| DC
INPUT / INTERNAL BATTERY |
| External
DC input: |
Nominal
22 to 32 VDC |
| External
DC control/protection: |
Guarded
2 pole switch (S3) w/rear mounted fuse (F3) |
| External
DC connector: |
MS 3102A-24-9P,
2 pin, locking |
| Internal
battery type: |
Maintenance
free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
| Internal
battery life: |
Rated
for continuous service life of 5 years |
| Internal
battery protection: |
Rear
panel mounted fuse (F1) |
| Internal
battery time: |
10+ minutes
@ 1000 watt load, 20+ minutes @ 50% |
| Internal
battery recharge: |
Recharged
to nominal in <8 hours |
| Internal
battery replacement: |
Drawout/plug-in
module from front of unit |
| DISTRIBUTION PANEL |
| Output
circuits: |
Six outputs
standard, optional configurations |
| Output
control: |
Guarded
3 pole switch (S5) |
| Output
receptacles: |
Metal
shell NEMA 5-15R, 3 pin locking, other options |
| MECHANICAL |
| Dimensions
( H x D x W ): |
7.00
(4U) x19.0 x 19.0 in (178 x 483 x 483 mm) |
| Rack
Slide Mount Patterns: |
Jonathan,
General Devices, others optional |
| Alternate
Mounting Options: |
Table,
Wall, Floor, Portable, Horizontal/Vertical |
| Unit
weight: |
98 lb.
(45 kg) with lift handles front and rear |
| Audible
noise: |
Less
than 47 dB @ 5.0 ft., ANSI "A" scale |
| Cooling
type: |
High
capacity, negative pressure, forced air |
| Cooling
air direction: |
Front
intake, exhaust to rear |
| Air intake
filter: |
Washable
metal filter media, others optional |
| ENVIRONMENTAL |
| Storage
temperature: |
-13° to
140° F ambient (-25° to 60° C) |
| Operating
temperature: |
50° to
104° F ambient ( 10° to 40° C) |
| Operating
humidity: |
0 to
95% relative humidity (non-condensing) |
| Storage
elevation: |
Up to
40,000 ft (12,192 m), higher optionally |
| Operating
elevation: |
Up to
10,000 ft (3,048 m), higher optionally |
| STANDARDS |
| United
States: |
Meets
UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A &
MIL-S-901 |
| Canada: |
CSA C22.2
No. 107 UPS safety requirements |
| EMI Protection: |
EMI/RFI
FCC, Class A; EN55022; MIL STD 461 |
| OPTIONAL ACCESSORIES |
| |
Emergency
Power Off, Elapsed Time Meter, Cold Start, Alternate
I/O Configurations, Dual Source Input, Battery
Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power
Distribution Units, Software
Interface, 10BaseT Ethernet SNMP/HTTP
port, Transport
Cases |