Technical
Specifications:
P/N: ETI0001-1259
| AC
OUTPUT |
| Output
voltage: |
120
VAC true sinewave std, up to 600 VAC optional |
| Output
rating: UPS |
1550
VA, standard in 4U x 19" chassis
0.65-0.75 pf std, optional configurations to 24,000 VA |
| Non-linear
load capacity: |
Up
to 100% non-linear load capability w/o derating |
| Output
voltage regulation: UPS |
± 3.0%
static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
| Overload
surge capacity: |
110%
for 10 minutes; 125% for 30 seconds |
| Harmonic
distortion: |
Less
than 5.0% into 100% non-linear load |
| Output
frequency: UPS |
60
Hz ± 1.0% independent of input frequency |
| Operational
status |
Status,
load and battery (16) LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off |
| AC
INPUT |
| Input
voltage selection: |
Autoranging
from nominal 115 VAC to 230 VAC |
| Input
voltage tolerance: UPS |
+15%
-25%, or 85-135 and 170-270 |
| Input
frequency: |
From
46 Hz to 440 Hz |
| Input
power factor: |
Better
than 99% typically |
| Input/output
isolation: |
2000
VA, >120 dB common mode, <1.0 ma leakage |
| Input
transient suppression: |
Complies
with IEEE 587 and UL 1449 |
| Input
control/protection: |
Guarded
2 pole switch (S1) w/fuse (F2) |
| Input
power connection: |
MS
3102A-22-2P, 3 pin, locking |
| DC
INPUT / INTERNAL BATTERY |
| External
DC input: |
Nominal
22 to 32 VDC |
| External
DC control/protection: |
Guarded
2 pole switch (S3) w/rear mounted fuse (F3) |
| External
DC connector: |
MS
3102A-24-9P, 2 pin, locking |
|
Internal
battery type: |
Maintenance
free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
| Internal
battery life: |
Rated
for continuous service life of 5 years |
| Internal
battery protection: |
Rear
panel mounted fuse (F1) |
| Internal
battery time: |
10+
minutes @ 1000 watt load, 20+ minutes @ 50% |
| Internal
battery recharge: |
Recharged
to nominal in <8 hours |
| Internal
battery replacement: |
Drawout/plug-in
module from front of unit |
| DISTRIBUTION
PANEL |
| Output
circuits: |
Six
outputs standard, optional configurations |
| Output
control: |
Guarded
3 pole switch (S5) |
| Output
receptacles: |
Metal
shell NEMA 5-15R, 3 pin locking, other options |
| MECHANICAL |
| Dimensions
( H x D x W ): |
7.00
(4U) x19.0 x 19.0 in (178 x 483 x 483 mm) |
| Rack
Slide Mount Patterns: |
Jonathan,
General Devices, others optional |
| Alternate
Mounting Options: |
Table,
Wall, Floor, Portable, Horizontal/Vertical |
| Unit
weight: |
98
lb. (45 kg) with lift handles front and rear |
| Audible
noise: |
Less
than 47 dB @ 5.0 ft., ANSI "A" scale |
| Cooling
type: |
High
capacity, negative pressure, forced air |
| Cooling
air direction: |
Front
intake, exhaust to rear |
| Air
intake filter: |
Washable
metal filter media, others optional |
| ENVIRONMENTAL |
| Storage
temperature: |
-13° to
140° F ambient (-25° to 60° C) |
| Operating
temperature: |
50° to
104° F ambient ( 10° to 40° C) |
| Operating
humidity: |
0
to 95% relative humidity (non-condensing) |
| Storage
elevation: |
Up
to 40,000 ft (12,192 m), higher optionally |
| Operating
elevation: |
Up
to 10,000 ft (3,048 m), higher optionally |
| STANDARDS |
| United
States: |
Meets
UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A &
MIL-S-901 |
| Canada: |
CSA
C22.2 No. 107 UPS safety requirements |
| EMI
Protection: |
EMI/RFI
FCC, Class A; EN55022; MIL STD 461 |
| OPTIONAL
ACCESSORIES |
| |
Emergency Power Off, Elapsed Time
Meter, Cold Start, Alternate I/O Configurations, Dual
Source Input,
Battery
Expansion, Batteryless Operation,
Battery
Charger/Conditioner,
Power
Distribution Units,
Software
Interface, 10BaseT Ethernet SNMP/HTTP port,
Transport
Cases |