Part
Number:
ETI0001-2227AC Rugged
MilSpec 1000 VA
Rackmount UPS
w/Global Inputs and Intelligent Interface
|
All
Rackmount UPS Products:
|
 |
|
USMC / Lockheed Martin HMMWV Configuration
WorldPower™ Rugged MilSpec Rack Mount 1.0 kVA UPS
Autoranging Global Isolated Input Accepts 85-270 VAC, 46-70 Hz
Or 22-32 VDC
Input from HMMWV or other Military Vehicle
Input PFC, Battleshort, Manual Bypass, Elapsed Time,
Wide Temp
SNMP / HTTP Interface
Plus Front Access Hot Swappable Battery

P/N:
ETI0001-2227AC
Rugged MilSpec UPS Standard Front Panel Layout

P/N: ETI0001-2227AC
Rugged MilSpec UPS Standard Rear Panel Layout
The field proven WorldPower™ UPS line is ideally suited for
military, industrial, computer and telecommunications
applications requiring high reliability, rugged
construction, compact size and light weight design. These
units are equally suited for use in shipboard, airborne,
vehicular, field deployed or fixed locations with controlled
or uncontrolled environments. The ETI0001-2227AC
is specifically designed for lightweight global power by the
US Navy as the power source for critical systems because of
the stringent performance and reliability requirements.
The heavy-duty
chassis, occupying only 5.25”(3U) of rack space while
delivering up to 1000 VA of clean, uninterruptible power.
The rounded metal corners and rugged handles front and
rear, aid in safe handling. Internally, all major components
are well secured and electrically insulated to prevent
damage due to shock and vibration. These units can be mounted
horizontally or vertically. Optional heavy-duty rack slides
provide easy installation and removal of the unit with
full extension.
The internal
shielded input transformer provides galvanic isolation
with provisions for both domestic (115 VAC, CONUS) and
international (230 VAC, OCONUS) input voltages. The autoranging
input voltage selection allows inputting either 115 VAC
or 230 VAC without having to open the UPS enclosure. Special
EMI/RFI filters and input power factor correction minimize
both input current and harmonics. The unit also operates
as a frequency converter, taking 46-70 hertz input and
converting it to clean, uninterruptible 60 hertz power.
Optionally, 46-440 hertz input as well either 50 or 400
hertz outputs are available. Alternately, the unit also
accepts vehicular or aircraft power from nominal 24 VDC
systems.
The LED
arrays keep the operator informed as to the unit's status
including load and battery levels. The Elapsed Time Indicator
records the number of operational hours for records and
scheduling preventative maintenance of attached equipment.
The front panel also provides easy access to both the AC
Input and Battery Input fuses. Coupled with the adjacent
spare fuses, MTTR is reduced to less than 15 minutes.
The internal
intelligent thermal sensors provide two stage monitoring
of unit temperatures, with both local and remote Battleshort
override capability of thermal shutdown. Battleshort can
be engaged via the front panel control, via a remote contact
input or via a software command. When in Battleshort, an
audible alarm is sounded and an indicator is lit. The high
intensity audible alarm can be heard in high noise environments
and includes an audible enable/disable switch.
All
controls and protective devices are brought to the front and
rear panels with critical switches or circuit breakers
having finger guards. Further, all front panel devices are
recessed to prevent damage or accidental operation. Clips on
the front panel hold spare fuses for ready access. The input
circuit breaker and the galvanic isolation transformer all
provide a double pole isolated source for shipboard systems
or overseas locations where phase references and grounding
are not consistent. The manual bypass feature included is
operated from the front panel. Even in the bypass mode, the ETI0001-2227AC
still provides galvanic isolation, transient surge
protection and EMI/RFI filtering.
The ETI0001-2227AC
has the added benefit of having a field replaceable battery
via front drawout battery module. The battery is a true
hot-swappable module and does not require going to bypass
like competing units. Even with this battery module removed,
this UPS can continue to operate as an electronic power
conditioner and frequency converter, providing clean, well
regulated, sinusoidal power to the load. The batteries are
maintenance free with immobilized electrolyte and are
constructed of flame retardant materials for added safety.
For more information, see the
Battery Technology
section.
The rear
panel provides locking connectors for the input and output
power with various optional configurations available. This
unit draws air through the front air filter and exhausts
out the rear vent into the rack. This allows the unit to
be used in negative or neutral pressure racks. For positive
pressure racks, rear to front or rear to side versions are
available. A removable and washable intake air filter and
high capacity stainless steel ball bearing fan provide added
protection in both controlled and hostile environments.
The RJ45 LAN port provides an SNMP/HTTP
interface for various UPS parameters and control of the load outputs.
Internal software functions include the ability to Sequence Loads of Startup and
to Shed Loads for either Overload, or Overtemperature or to lengthen battery run
time (when used with battery modules). These functions follow a user defined
priority lists and schedules.
The status D shell connectors provide both a contact
and serial interface with optional
computer
software providing loss of AC and low battery status
as well as remote shut down capability. See
the Power Distribution Units section
for a listing of stand alone PDUs. See the N5 Series for
a version of this UPS with an integrated PDU and remote
control
Overall,
the PowerStation line is uniquely qualified for critical
shipboard, vehicle, airborne or land based systems combining
advanced modular design features with highly reliable construction.
Technical
Specifications:
P/N: ETI0001-2227AC
| AC
OUTPUT |
|
Output
voltage: |
120
VAC true sinewave output standard |
|
Output
rating: UPS |
1000
VA, 750 watts standard,
For 1000 VA, 750 watts, see ETI0001-2227
(w/o DC Input)
For 1500 VA, 1150 watts, see
ETI0001-2228
For 2000 VA, 1500 watts, see ETI0001-2229 |
|
Non-linear
load capacity: UPS |
Up
to 100% non-linear load capability w/o derating |
|
Output
voltage regulation: UPS |
± 3.0%
static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
|
Overload
surge capacity: UPS |
110%
for 10 minutes; 125% for 30 seconds |
|
Harmonic
distortion: UPS |
Less
than 5.0% into 100% non-linear load |
|
Output
frequency: UPS |
60
Hz ± 2.5% synchronized to utility
60 Hz ± 1.0% w/ utility not available |
|
Operational
status |
AC
Input status, UPS operational, UPS alarm, Battery level,
Low battery, Load level, Overload, Warm temperature,
Hot temperature, Manual bypass and Battleshort LEDs,
Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
+90 dB audible alarm with audible on/off switch
Asynchronous serial COM port |
|
AC
INPUT |
|
Input
voltage selection: |
Autoranging
from nominal 115 VAC to 230 VAC |
|
Input
voltage tolerance: UPS |
+15%
-25%, or 85-135 and 170-270
@ full load without using battery, to 70 VAC @ 75% load |
|
Input
frequency: |
From
46 Hz to 70 Hz standard, optional to 440 Hz |
|
Input
power factor: |
Better
than 99% typically |
|
Input/output
isolation: |
2000
VA, up to 120 dB common mode, <1.0 ma leakage |
|
Input
transient suppression: |
Complies
with IEEE 587, UL 1449 and Mil Std 1399 |
|
Input
control/protection: |
Guarded
2 pole 100 G shock rated circuit breaker (CB1)
plus UPS input fuse (F2), spare fuse on front
Manual bypass switch to force bypass mode
Optional cold start switch available to turn on w/o AC present |
|
Input
power connections: |
One
MS 3102A-22-2P, 3 pin, locking |
| DC
INPUT / INTERNAL BATTERY |
| External
DC input: |
Nominal
22 to 32 VDC |
| External
DC control/protection: |
Guarded
2 pole switch (S3) w/rear mounted fuse (F3) |
| External
DC connector: |
MS
3102A-24-9P, 2 pin, locking |
|
Internal
battery type: |
Maintenance
free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
|
Internal battery life: |
Rated
for continuous service life of 5 years |
|
Internal battery
protection: |
Front
panel mounted fuse (F1), spare fuse on front |
|
Internal
battery time: |
10+
minutes @ 1000 watt load, 20+ minutes @ 50% |
|
Internal
battery recharge: |
Recharged
to nominal in <8 hours |
|
Internal
battery replacement: |
Hot
swap drawout/plug-in module from front of unit
<3 minutes to change battery modules |
|
Battery
expansion: |
Up
to 24 hours w/ optional Battery Expansion Modules |
|
DISTRIBUTION
PANEL |
|
Output
circuits: |
Six
AC outputs standard, several optional configurations |
|
Output
control: |
Only
via CB1;optional remote control panel w/switches
optional |
|
Output
receptacles: AC output |
MS threaded locking standard, various
options |
|
MECHANICAL |
|
Dimensions
(H x D x W): UPS |
5.25
(3U) x 23.5 x 19.0 in (133 x 597 x 483 mm) |
|
Rack
Slide Mount Patterns: |
Jonathan,
General Devices patterns standard, others optional |
|
Alternate
Mounting Options: |
Table,
Wall, Floor, Portable, Horizontal/Vertical |
Unit
weight:
UPS and Battery
UPS
only
Battery
Module only |
88
lb. (40 kg) with lift handles front and rear
60 lb. (27 kg) with lift handles front and rear
28 lb. (13 kg) with lift handle in front |
|
Audible
noise: |
Less
than 47 dB @ 5.0 ft., ANSI "A" scale |
|
Cooling
type: |
High
capacity, negative pressure, forced air |
|
Cooling
air direction: |
Front
intake, exhaust to rear, others optional |
|
Air
intake filter: |
Washable
metal filter media, others optional |
|
ENVIRONMENTAL |
|
Storage
temperature: |
-40° to
158° F ambient (-40° to 70° C) |
|
Operating
temperature: |
32° to
126° F ambient ( 0° to 52° C), lower/ higher optional |
|
Operating
humidity: |
0
to 95% relative humidity (non-condensing) |
|
Storage
elevation: |
Up
to 40,000 ft (12,192 m), higher optional |
|
Operating
elevation: |
Up
to 10,000 ft (3,048 m), higher optional |
|
STANDARDS |
|
United
States: |
Meets
UL-1778 standard for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A &
MIL-S-901 |
|
Canada: |
CSA
C22.2 No. 107 UPS safety requirements |
|
EMI
Protection: |
EMI/RFI
FCC Part 15, Class A; EN55022; MIL STD 461 |
|
OPTIONAL
ACCESSORIES |
|
|
Emergency Power Off, Elapsed Time
Meter, Cold Start, Alternate I/O Configurations, Dual
Source Input,
Battery Expansion,
Battery Charger/Conditioner,
Power Distribution Units,
Software Interface, Transport Cases,
Batteryless Operation |
This
page was last modified on:
May 17, 2008
|