| AC
OUTPUT |
| Output voltage (standard): |
120 VAC true sinewave
output standard setting
100 or 110 VAC optional settings available |
| Output voltage (optional): |
220, 230 or 240 VAC
version available, see ETI0019-2110EC |
| Output rating (standard): |
1000 VA, 700 watts
standard |
| Output rating (optional): |
2000 VA, 1500 watts
version available, see ETI0019-2120EA |
| Non-linear load capacity: |
Up to 100% non-linear
load capability w/o derating |
| Output voltage regulation: |
± 3.0% static regulation
of nominal
± 5.0% dynamic (0 to 50% load step) |
| Overload surge capacity: |
110% for 10 minutes;
125% for 30 seconds |
| Harmonic distortion: |
Less than 5.0% into
100% non-linear load |
| Output frequency: |
60 Hz or 50 Hz switch
selectable
|
| Operational status: |
AC Input status, UPS
operational, Battery level, Low battery,
Load level, Overload LEDs, audible alarm w/audible on/off
switch |
| AC
INPUT |
| Input voltage (AC
Input): |
Autoranging from nominal
90 VAC to 264 VAC |
| Input frequency: |
From 47 Hz to 63 Hz
standard, optional up to 440 Hz |
| Input power factor: |
Better than 95% typically |
| Input/output isolation: |
up to 120 dB common
mode, <2.0 ma leakage |
| Input transient suppression: |
Complies with IEEE
587, UL 1449 and Mil Std 1399 |
| Input control/protection: |
Guarded circuit breaker
|
| Input power connections: |
One IEC 60320-C14
male, 3 pin with cable restraint |
| Input power cable: |
One 6' cord w/IEC
60320-C13 female and NEMA 5-15P |
| Input power cable
adapters: |
One kit of universal
plug adapters for most global outlets |
| DC
INPUT / INTERNAL BATTERY |
| External DC input (standard):
24 VDC |
Nominal 21 to 30 VDC |
| External DC input (optional):
12 VDC |
Nominal 10.5 to 15 VDC version available,
see ETI0019-2110EB |
| External DC input (optional):
48 VDC |
Nominal 42 to 60 VDC version available,
see
ETI0019-2110EE |
| External DC control/protection: |
Thermal circuit breaker |
| External DC connector: |
CPC, 7 pin, locking |
| Internal
battery type: |
Maintenance free immobilized
electrolyte,
Flame retardant materials (Oxygen Index 28+) |
| Internal battery life: |
Rated for continuous
service life of 5 years |
| Internal battery time: |
10+ minutes @ 700
watt load, 20+ minutes @ 490 watts |
| Internal battery recharge: |
Recharged to nominal
in <8 hours |
| Internal battery replacement: |
Drawout/plug-in module
from front of unit
<5 minutes to change battery modules |
| Battery expansion: |
Up to 24 hours w/
optional Battery
Expansion Modules |
| DISTRIBUTION
PANEL |
| Output circuits: |
Four AC outputs standard,
several optional configurations |
| Output
protection (standard): |
One GFCI
(Ground Fault Circuit Interrupter) duplex, one
standard duplex |
| Output
protection (optional): |
Individual
push/pull circuit breakers available for each outlet |
| Output receptacles:
AC output |
NEMA 5-15R with dust
covers, others optional |
| MECHANICAL |
| Dimensions (H x D
x W): |
21.75 x 8.99 x 13.75
in (552 x 228 x 349 mm) |
Unit weight:
UPS and Battery
UPS only
Battery Module only |
50 lb. (23 kg) with lift handles front and rear
24 lb. (11 kg) with lift handles front and rear
26 lb. (12 kg) with lift handle in front |
| Audible noise: |
Less than 47 dB @
5.0 ft., ANSI "A" scale |
| Cooling type: |
High capacity, positive
pressure, forced air |
| Air intake filter: |
Washable filter media,
others optional |
| ENVIRONMENTAL |
| Storage temperature: |
-40° to 158° F ambient
(-40° to 70° C) |
| Operating temperature: |
32° to 126° F ambient
( 0° to 52° C), lower/ higher optional |
| Operating humidity: |
0 to 95% relative
humidity (non-condensing) |
| Storage elevation: |
Up to 50,000 ft (15,240
m), higher optional |
| Operating elevation: |
Up to 10,000 ft (3,048
m), higher optional |
| STANDARDS |
| United States: |
Meets UL-1778 standard
for UPS equipment,
Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A
& MIL-S-901 |
| Canada: |
Meets CSA C22.2 No.
107 UPS safety requirements |
| EMI Protection: |
Meets EMI/RFI FCC
Part 15, Class A; EN55022 |
| OPTIONAL
ACCESSORIES |
| |
Cold Start, Alternate
I/O Configurations, Battery
Expansion,
Battery
Charger/Conditioner, Power
Distribution Units |