AC
OUTPUT |
| Output
voltage (standard): |
120
VAC true sinewave output standard setting 100 or 110 VAC optional settings available |
| Output
voltage (optional): |
220, 230 or 240 VAC version
available, see
ETI0019-2120EC |
| Output rating (standard): |
2000 VA, 1500 watts standard |
| Output rating (optional): |
1000 VA, 700 watts version
available, see
ETI0019-2110EA |
| Non-linear load capacity: |
Up to
100% non-linear load capability
w/o derating |
| Output voltage regulation: |
± 3.0%
static regulation of nominal ± 5.0% dynamic (0 to 50% load
step) |
| Overload surge capacity: |
110%
for 10 minutes; 125% for 30 seconds |
| Harmonic distortion: |
Less
than 5.0% into 100% non-linear
load |
| Output frequency: |
60 Hz
or 50 Hz switch selectable
|
| Operational
status: |
AC Input
status, UPS operational, Battery
level, Low battery, Load level, Overload LEDs, audible
alarm w/audible on/off switch |
|
AC
INPUT |
| Input
voltage (AC Input): |
Autoranging
from nominal 90 VAC to 264 VAC |
| Input
frequency: |
From
47 Hz to 63 Hz standard, optional
up to 440 Hz |
| Input
power factor: |
Better
than 95% typically |
| Input/output
isolation: |
up to
120 dB common mode, <2.0 ma
leakage |
| Input transient suppression: |
Complies
with IEEE 587, UL 1449 and Mil
Std 1399 |
| Input
control/protection: |
Guarded circuit breaker |
| Input
power connections: |
One
IEC 60320-C14 male, 3 pin with
cable restraint |
| Input power
cable: |
One 6' cord
w/IEC 60320-C13 female and NEMA 5-15P |
| Input power
cable adapters: |
One kit of
universal plug adapters for most global outlets |
|
DC
INPUT / INTERNAL BATTERY |
| External DC input (standard):
24 VDC |
Nominal 21 to 30 VDC |
| External DC input (optional):
12 VDC |
Nominal 10.5 to 15 VDC version available, see
ETI0019-2120EB |
| External DC input (optional):
48 VDC |
Nominal 42 to 60 VDC version available,
see
ETI0019-2120EE |
| External DC control/protection: |
Thermal circuit breaker |
| External DC connector: |
CPC, 7 pin, locking |
|
Internal
battery type: |
Maintenance
free immobilized electrolyte, Flame retardant materials (Oxygen
Index 28+) |
| Internal
battery life: |
Rated
for continuous service life of
5 years |
| Internal
battery time: |
10+
minutes @ 700 watt load, 20+
minutes @ 490 watts |
| Internal
battery recharge: |
Recharged
to nominal in <8 hours |
| Internal
battery replacement: |
Drawout/plug-in module from
front of unit <5 minutes to change battery
modules |
| Battery
expansion: |
Up to
24 hours w/ optional
Battery
Expansion Modules |
|
DISTRIBUTION
PANEL |
| Output
circuits: |
Four AC outputs standard, several
optional configurations |
| Output
protection (standard): |
One GFCI
(Ground Fault Circuit Interrupter) duplex, one
standard duplex |
| Output
protection (optional): |
Individual
push/pull circuit breakers available for each outlet |
| Output
receptacles: AC output |
NEMA
5-15R with dust covers, others
optional |
|
MECHANICAL |
| Dimensions (H x D x W): |
21.75
x 8.99 x 13.75 in (552 x 228
x 349 mm) |
Unit
weight: UPS
and Battery UPS
only Battery
Module only |
50 lb. (23 kg) with lift handles
front and rear 24 lb. (11 kg) with lift handles
front and rear 26 lb. (12 kg) with lift handle
in front |
| Audible
noise: |
Less
than 47 dB @ 5.0 ft., ANSI "A" scale |
| Cooling
type: |
High
capacity, positive pressure,
forced air |
| Air
intake filter: |
Washable
filter media, others optional |
|
ENVIRONMENTAL |
| Storage
temperature: |
-40° to
158° F ambient (-40° to 70° C) |
| Operating
temperature: |
32° to
126° F ambient ( 0° to 52° C),
lower/ higher optional |
| Operating
humidity: |
0 to
95% relative humidity (non-condensing) |
| Storage
elevation: |
Up to
50,000 ft (15,240 m), higher
optional |
| Operating
elevation: |
Up to
10,000 ft (3,048 m), higher optional |
|
STANDARDS |
| United
States: |
Meets
UL-1778 standard for UPS equipment, Meets MIL-STDs 1275, 167-1, 454,
810, 1399-300A
& MIL-S-901 |
| Canada: |
Meets CSA
C22.2 No. 107 UPS safety requirements |
| EMI
Protection: |
Meets EMI/RFI
FCC Part 15, Class A; EN55022 |
|
OPTIONAL
ACCESSORIES |
| |
Cold
Start, Alternate I/O Configurations,
Battery
Expansion,
Battery
Charger/Conditioner,
Power